KNX Cybersecurity Checklist for Designers and Integrators
Use this KNX cybersecurity checklist to review IP exposure, KNX Secure scope, installer access, project backups, and evidence before building handover.

The room controls work. The owner has the tablet app. The installer can still connect remotely using an account created six months ago. Is the installation ready to hand over?
Not until somebody can explain who owns that account, how it is revoked, and what else the connection can reach.
A useful KNX security checklist follows the access paths into the building, then asks for evidence. Start with internet exposure, local network permissions, physical bus access, Secure configuration, and recovery. A device marked “Secure” is one component of that review; it is not the review itself.
This article is a practical design and acceptance framework. It does not certify an installation or replace a project-specific security assessment. Carry out connectivity tests only on systems you are authorized to assess, using an agreed scope and maintenance window.
Start with a one-page access map
List every route by which someone can read data, change a setting, or send a command. Include the routes that are convenient enough to be forgotten: a maintenance laptop, a visualization server, a vendor cloud connector, and an Ethernet socket in a publicly accessible cupboard.
| Access path | Question to resolve | Evidence to keep |
|---|---|---|
| Remote maintenance | Who grants access, for how long, and to which hosts? | Approved access policy and named account owner |
| KNX IP interfaces and routers | Which networks may reach the required services? | Address inventory and approved firewall rules |
| Visualization or integration server | What can it write, and which credentials does it hold? | Service-account scope and integration register |
| Physical TP bus and cabinets | Can visitors reach terminals or programming interfaces? | Cabinet access plan and inspection record |
| Project files and certificates | Who can recover, export, or redistribute them? | Protected storage location and access list |
Do not put passwords or device secrets into this table. Record where they are held and who controls access. A handover spreadsheet should not quietly become an unencrypted credential store.
The KNX Association security checklist is a useful official baseline. Add project-specific systems to it, especially integrations that sit outside the KNX bus.
Close the internet path before polishing the dashboard
KNX Association’s guidance on securing the IP side warns against exposing KNXnet/IP directly to the internet and identifies UDP port 3671 as its usual port. A local service using that port is not, by itself, evidence of a vulnerability. The question is which untrusted networks can reach it.
Ask the network administrator to review port forwarding, firewall rules, VPN permissions, and any vendor remote-access service. Do not assume that changing a public port number provides meaningful protection.
For a proposed maintenance arrangement, write the intended behavior in plain language: “The named service engineer may connect through the approved remote-access system to the designated engineering host during an authorized support session.” Then check whether the configuration actually limits access that way.
Network separation helps reduce exposure. It does not encrypt KNX payloads, authenticate every application, or make a compromised engineering laptop harmless. Likewise, a VPN is an access mechanism, not permission to give every connected user unrestricted access to all building systems.
Check what is secured, not just what was purchased
KNX IP Secure protects KNX communication on the IP transport, while KNX Data Secure protects application communication between participating devices. Those are different boundaries. The Association’s security overview explains this distinction and the related authentication, integrity, and confidentiality functions.
| Design question | What to inspect in the actual project | What not to assume |
|---|---|---|
| Is the IP routing path protected? | Supported routers, enabled Secure configuration, participating endpoints | An isolated VLAN is equivalent to IP Secure |
| Are selected group communications protected? | Compatible Data Secure endpoints and object configuration | A secure router encrypts every TP device exchange |
| Can the BMS or visualization participate? | Supported secure interface and documented credential handling | A third-party integration automatically inherits protection |
| Are legacy devices present? | Documented non-secure functions and accepted boundaries | One new secure device upgrades the whole line |
| Can another engineer maintain the system? | Recoverable project and authorized access to required secrets | Security should depend on one installer’s laptop |
Keep the assessment tied to functions. “Bedroom lighting uses these endpoints and this communication path” is reviewable. “The building is secure” is too broad to test.
For a deeper protocol comparison, see KNX Data Secure vs KNX IP Secure.
Use acceptance gates with an owner
The following is a suggested project checklist, not a KNX certification procedure. Each row needs a responsible person and a result: pass, open issue, or accepted exception with a reason.
| Gate | Acceptance question | Suggested responsible party |
|---|---|---|
| Asset inventory | Do model, firmware, address, location, and support contact match installed equipment? | Integrator |
| Network access | Are approved paths available and prohibited paths blocked? | Building IT / network contractor |
| Physical access | Are cabinets, network sockets, and exposed bus connections appropriately controlled? | Electrical contractor / facilities |
| Account cleanup | Have temporary and shared installer accounts been removed or explicitly retained? | System owner |
| Secure commissioning | Are required certificates and configuration recoverable through protected storage? | Integrator and owner |
| Integration permissions | Can each service perform only its agreed tasks? | Integration supplier |
| Recovery | Can an authorized maintainer locate and open the current protected project backup? | Facilities / maintenance provider |
| Support lifecycle | Who receives advisories and approves updates or replacement? | Owner’s nominated service lead |
Avoid ticking “backup complete” because an export file exists. Check the file version, the recovery credentials, and who can access both. Perform any restore or device-replacement exercise in a safe test environment or an approved outage; a production download is not a harmless backup test.
A small example: retiring temporary commissioning access
Suppose a contractor uses a remote account to commission a hotel floor. After acceptance, the owner wants emergency support available but does not want permanent installer access.
The closeout record could contain four decisions:
- Disable the temporary account after the agreed acceptance window.
- Keep the remote-access platform under the owner’s administration.
- Issue named, time-bounded access for future service work.
- Store the final ETS export and recovery instructions in the owner’s protected repository.
The evidence is a recorded account-state check and an authorized access test, not a screenshot showing that the lights still switch. Emergency support also needs a contact and approval process; otherwise the next urgent fault is likely to produce an undocumented workaround.
Treat changes as a security event
Adding a dashboard can introduce more risk than adding several room sensors because it may bridge networks, hold credentials, and expose a web service. Revisit the access map when an integration, tenant, maintenance company, or remote-access method changes.
For firmware maintenance, record the installed version, vendor advisory, proposed action, rollback or recovery route, and functional checks. Do not apply an untested update during occupied operation merely to make a version number current. Equally, do not leave an identified security issue without an owner and a decision date.
Keep the security closeout with the KNX documentation and handover package, not in an email thread that disappears when the project team changes.
Questions at the handover meeting
Is KNX Secure enough without network controls?
No. Secure communication and network access controls address different risks. The engineering workstation, integration services, credentials, and physical installation still require attention.
Should all external access be removed?
Not necessarily. Remote support may be useful, but it should be explicitly approved, restricted, attributable to named users, and revocable. Undocumented permanent access is the problem.
Can this checklist prove that the installation cannot be attacked?
No. It provides a structured evidence trail for design and handover. Higher-risk buildings may need an independent assessment with a defined scope, qualified assessors, and operational safeguards.
If the project is still at design stage, include these gates in the commissioning plan. For a device or integration review, send KNXmart the topology and access requirements, without sending passwords or private device certificates through a general inquiry form.