KNX CO2, Temperature, and Humidity Sensor Selection
Compare KNX CO2, temperature and humidity sensors by measurement method, placement, ETS objects, calibration, and ventilation control behavior.

A meeting room can have a perfectly good CO₂ sensor and a poor CO₂ reading. Mount it outside the door and it will track the corridor. Put it beside a supply grille and it may mostly see fresh supply air. The controller will follow either number quite happily.
For a KNX CO₂ sensor, start by defining the air the sensor should represent and the decision its readings will drive. Direct CO₂, room temperature, and relative humidity serve different jobs. A three-in-one unit works well where one location suits all three, the ETS application exposes the values you need, and someone owns the response when a reading goes stale.
Decide what the room needs to measure
| Reading | Typical control use | Check before specifying |
|---|---|---|
| Direct CO₂ in ppm | Ventilation demand in occupied meeting rooms, classrooms, or offices | Measurement principle, accuracy at the operating range, calibration behavior |
| Air temperature in °C | Room-temperature control, setpoint display, trending | Mounting conditions, sensor offset, accuracy, and source of the temperature loop |
| Relative humidity in % RH | Humidity-driven extraction or a comfort trend | Accuracy near the limits of interest, condensation restrictions, and location |
| VOC or air-quality index | Additional cue for a control sequence that responds to that index | What the index represents, its scale, and whether it is a separate object |
| Calculated dew point | Input to a condensation-risk assessment | Source readings and the independent surface or water temperature needed for the comparison |
Ask whether the product measures CO₂ directly, such as by non-dispersive infrared (NDIR), or estimates an equivalent value from another measurement. The two can behave quite differently when cleaning chemicals or furnishings affect VOC readings. Keep the two point names distinct in ETS and on the dashboard. The MDT combi-sensor data sheet, for example, lists CO₂ in ppm and VOC as a separate indoor-air-quality index. MDT combi sensor data sheet
Read the accuracy specification as well as the range. If the ventilation sequence changes stage over a narrow band, look at the device’s accuracy, repeatability and drift in that band. A display that shows an integer ppm value tells you its resolution. The data sheet tells you how much confidence to place in it.
CO₂ is useful as an indicator of how occupied spaces are ventilated when people are the main source. Its interpretation depends on occupancy, activity, mixing, and outdoor concentration. A single reading has limited value as an overall air-quality assessment. UK HSE guidance on CO₂ monitoring
Mark the sensing position on the drawing
For a regularly occupied room, start with a representative position around the occupied breathing zone, then check the manufacturer’s mounting instructions. Watch for outside doors, windows, supply jets, direct sunlight, and a chair that places someone’s face right next to the sensor. UK HSE makes similar siting recommendations for portable monitors. Use those principles to judge the room and the product instructions to choose the permanent installation. HSE guidance on monitor placement
For temperature, consider what is inside the wall or enclosure as well. A warm power supply, a draft through a wall box, or a sunlit wall can bias the temperature point. Compare candidate locations before relying on an offset. An offset can correct a consistent bias at the conditions checked. It will struggle with a bias that reverses when the sun moves.
On a large floor with several ventilation zones, assign each sensor to the zone whose demand it can represent. A return-duct reading can be useful for an aggregate trend, but mixing can conceal one crowded room. If two sensors serve one zone, specify which controls it and how disagreement is handled. A maximum and an average lead to different behavior.
Write the point list before the controller sequence
| ETS point | What to verify in the actual application | Acceptance evidence |
|---|---|---|
| CO₂ actual value | Correct unit and data type, change reporting, cyclic refresh | Bus value and displayed ppm agree |
| Room temperature | Source, offset and compatible object | Compared with a suitable reference at a representative location |
| Relative humidity | Correct scale and independent update settings | Trend follows a plausible ambient change |
| Ventilation demand | One writer, defined stage or percentage, explicit priority | Output and fan or damper feedback agree with the sequence |
| Measurement status | Available fault object or timeout based on valid updates | Controller enters the specified fallback and recovers on fresh data |
Some devices can send on a measured change and also retransmit cyclically. Theben’s AMUN application manual shows separate settings for these behaviors and a manufacturer-specific fresh-air calibration procedure. Distinguish the change threshold, which limits telegram volume, from the cyclic interval used for freshness monitoring. Budget the resulting traffic if the same design is repeated across a floor of rooms. Theben AMUN KNX application manual
For example, two-minute cyclic reporting and a seven-minute timeout would allow several expected reports to be missed before the receiving controller changes state. These are example timing values. Pick the interval and timeout from the approved ventilation sequence and the selected devices. On startup, the receiving controller should apply its defined default until it receives a valid value. A dashboard should preserve the difference between a current value and a stale one. The KNX datapoint guide covers the object mapping.
Commission one occupied room first
Trend the sensor value, the controller’s demand, and whatever confirmation the ventilation system provides. A demand rising while the actual damper remains parked is an output or plant issue. A sensor staying flat while an independent reading changes may point to siting, warm-up, or send settings. An isolated spot reading cannot resolve either case.
- Show that ETS and the display agree on units and that the correct room name follows the point.
- Compare the installed sensor with a suitable reference after stabilization. Follow each manufacturer’s calibration instructions.
- Exercise the demand sequence using an approved test mode. Record the rise, release, and reset behavior along with actuator feedback.
- Test missing telegrams and recovery during an agreed window. Log the last valid value, fallback demand, and first valid value after restoration.
- Where practical, trend a normal occupancy period. Keep occupancy and ventilation changes in the log so the trend can be interpreted later.
Can a KNX CO₂ reading set ventilation by itself?
A room controller can use it to request ventilation within the mechanical design’s sequence. The HVAC designer still sets minimum airflow, operating limits, priority, and the fallback for a failed or missing sensor. Coordinate those decisions with the HVAC zoning plan.
When should temperature and CO₂ use separate sensors?
Separate them when the best location for one measurement compromises the other, or when the two measurements serve different zones or maintenance schedules. Confirm in the ETS project which device is the authoritative source for each quantity. A room schedule with location, measurement, consumer, and fallback makes a useful starting point for selection support. Contact KNXmart